Technical specifications of the UK fireguard beam detector:
The beam is certified by the fire department
It has EN54-12 certification
The beam detector is certified by the UK LPCB standard organization
Operating voltage: 20V to 28VDC
Beam current parameters:
Standard: 23mA
Command: 56mA
Warning: 33mA
Beam sensor sensitivity (via encryption):
Level 1: 2.6 dB (high sensitivity)
r\nLevel 2: 3.8 dB (medium sensitivity)
Level 3: 5.8 dB (low sensitivity)
Beam path length (via encryption) :
Coverage 1: 8 to 20 meters (limited path)
Coverage 2: 20 to 40 meters (short path)
Coverage 3: 40 to 70 meters (normal path)
Coverage 4: 70 to 100 meters (long path)
Light beam path angle: direction It has ±0.4° (this data is the average of left and right deviation angles)
Alignment guide: laser beam pointer
Digital display guide: Nixie Tube
Lamp status (LED):
Red : Fire
Yellow : Fault
Green : Aligned
Reset Time : Less than 2 seconds
Relay Capacity (Fire and Fault) : Normally open and close 30VDC, 2.0A\r\ Material / Color: ABS / White
Dimensions / Weight: L:190.87 x W:126.87 x H:91.96 mm / 440 gm
Working temperature: 10°C~+50°C–
Humidity: 0 to 95% relative humidity, non-condensing\r \nBeam detector 100 meters